Air Quality Matters artwork

Air Quality Matters · Simon Jones

Not All Faults Are Equal: A Data-Driven Guide to Prioritizing Building Maintenance for Better Air

This week, we dive into a study published in Building and Environment titled A Scalable Framework for Impact Analysis of Faults on Indoor CO2 in Buildings, to explore a question that fundamentally challenges how we think about building maintenance and indoor air quality: What if the single biggest barrier to delivering healthy indoor environments isn't our lack of technology or standards—but our complete failure to recognise that the faults we routinely ignore in HVAC systems are actively degrading the air we breathe, and we've had no systematic way to prioritise which faults actually matter until now? Key Topics Discussed: The Correlation Versus Causation Problem: In a building, everything is connected. If you just look at raw data, you might see counterintuitive things. For example, when the outdoor air damper is wide open, CO2 levels might actually be higher. A simple correlation analysis might conclude that opening the damper causes CO2 to rise, which makes no physical sense. What's actually happening is demand controlled ventilation. The system opens the damper because CO2 is rising. High CO2 is causing the damper to open, not the other way around. It's a classic feedback loop. To get around this simultaneity bias, the researchers used a clever approach called double machine learning. They stripped away all the noise and confounding variables like building ID, time of day, weather and current CO2 baseline, so they could isolate the true causal impact of a specific fault on CO2 levels. The Worst Faults for Air Quality: The absolute worst fault for indoor air quality is an AHU discharge fan failure. When the fan isn't generating the static pressure needed to move air, supply airflow drops off a cliff and return air CO2 spikes. The next worst is a poorly tuned system where the outside air damper is oscillating wildly, constantly cycling back to its closed position, severely reducing the overall volume of fresh air entering the building. Then there are valve leaks. A leaking cooling valve causes the supply air temperature to drop too low. The control system opens the heating valve and closes the outside air damper to keep warm air in. Because of a leaking cooling valve, your fresh air intake gets choked off and indoor CO2 shoots up. A leaking heating valve does the opposite. It opens the outside air damper to take advantage of free cooling, which actually dilutes indoor CO2 and improves air quality, but at a massive energy penalty. Zone Level Faults: At the zone level, the worst fault is terminal unit airflow set point unreachable low. This is when the VAV box damper is stuck or there's a ductwork issue, and the actual airflow to the room is consistently lower than what the thermostat is asking for. You get localised underventilation and zone CO2 spikes dramatically because fresh air is simply not getting into the space. The Prioritisation Framework: In facility management, we are constantly bombarded with fault alerts. In a large...

Sep 112026
11 minlength
99transcript lines
Publishertranscript source

Transcript first 15 of 99 lines

0:15Welcome back to Air Quality Matters and One Take.

0:18One Take, my take on a paper or report on air quality, ventilation and the built environment.

0:23I'm Simon Jones and today we're looking at a piece of work that gets right to the heart of what we do in the real world when managing buildings.

0:31It's a paper published in Buildings and Environment called A Scalable Framework for Impact Analysis of Faults on Indoor CO2 in Buildings.

0:41Now, that might sound a bit academic or a bit dry at first, but trust me, this is anything but dry.

0:48It's a massive real world study that analysed over 90 million rows of data from building automation systems across 23 commercial buildings in the US.

1:01Think about that for a second.

1:0390 million rows of actual operational data.

1:07And what they were looking at is something we talk about all the time on this show.

1:12The gap between what a system is designed to do and what it actually does on the ground.

1:18Specifically, they wanted to understand how common HVAC faults, the stuck dampers, the leaking valves, the failing fans, actually impact the air we breathe.

1:30We've had plenty of studies looking at how faults waste energy, but empirical evidence linking these faults to actual indoor air quality and specifically CO2 levels has been really hard to come by until now.

1:46What I love about this paper is how it tackles a really thorny problem in data analysis.

1:51And it's a concept I want to spend a minute on because it's so important.

1:55It's the difference between correlation and causation.